Faast Flex 1-channel inhalation sensing

XTRALIS-37

FLX-010


  • Faast Flex xtralis autonomous detection by apiration
  • 1 independent pipe
  • Area coverage up to 1600 m²
  • Adjustable fan
  • Sensor sensitivity from 0.05 %obs/m to 6.56 %obs/m
  • Class A, B and C performance (5, 15 and 32 orifices)
  • Incorporates ultrasonic sensor to control the flow of each channel
  • 3 relays per channel: action, alarm and fault
  • USB communication
  • Bluetooh interface with application for mobile devices for quick configuration and diagnostics
  • Power supply: 24V DC (18V ~ 30V DC)
  • Consumption: 400 mA at 24V DC
  • Operating temperature from -40°C ~ +55°C (-40°C ~ +55°C)
  • Sampled air temperature from -40°C ~ +55°C
  • Relative humidity 10% ~ 93%.
  • Degree of protection IP40
  • Dimensions: 205 (W) x 280 (H) x 80,5 mm
  • Weight: 1.7 kg
REFERENCE / MODEL XTRALIS-37 / FLX-010
Number of pipes 1
Estimated delivery: 1 to 5 business days (depending on the country)
Repair services and technical support
No worries: 15 days right of withdrawal
Secure transaction
xs
sm
md
lg
xl