honeywell
MORLEY-149 | MorleyIAS optical-thermal-IR multi-criteria detector with isolator
MORLEY-149MI-PTIR-S2IMorleyIAS optical-thermal-IR multi-criteria detector with isolator

MorleyIAS optical-thermal-IR multi-criteria detector with isolator

MORLEY-149

MI-PTIR-S2I

Main features

  • Analog detector with triple sensor for smoke, heat and IR flame
  • Decadic address 1-159
  • Compatible with CLIP and Advanced protocols
  • Verification algorithm in 6 levels
  • 360° multicolor LED
  • Pure white color
  • EN54-5/7

Specifications

  • Multi-criteria analog optical, thermal and flame detector (IR)
  • 6 alarm levels configurable by algorithm
  • Decadic addressing 1 to 159 with MorleyIAS-S200 protocol (Clip 1 to 99)
  • Dirt-immune camera with flame IR radiation verification
  • Anti-dirt and anti-insect filter made of polyethylene film
  • Dual multicolor LEDs visible 360° for communication and alarming
  • Incorporates loop short-circuit isolator
  • Remote indicator light output
  • Magnet alarm test by signal amplification
  • Compatible with all MorleyIAS analog bases, including base with tube, siren or flash input
  • Extra slim PC+ABS flame-retardant plastic design
  • Color: pure white
  • Supply voltage: 15-32 VDC
  • Standby consumption: 200 μA (at 24 V, LED off)
  • Consumption in communication: 300 μA (LED every 5 s)
  • Maximum LED consumption:
    • Red: 3.5 mA
    • Green: 7 mA
    • Yellow: 10.5 mA
  • Remote output: 22.5 VDC / 10.8 mA (at 24 V loop)
  • Thermal activation according to EN54-5 Class A1R (58 °C)
  • Smoke activation according to EN54-7 (microprocessor)
  • Operating temperature: -30 °C to +50 °C (-30 °F to +50 °C)
  • Relative humidity: 10 % to 93 % non-condensing
  • Compatible base: NOTIFIER-77 (B501AP)
  • Dimensions: 102 × 63 mm (with base)
  • Net weight: 102 g
  • Certifications: EN 54-5, EN 54-7, CPD, LPCB, WEEE, RoHS
REFERENCE / MODEL MORLEY-149 / MI-PTIR-S2I
Protocol Advanced || Clip
Detector Technology Multisensor
Base/Cover included NO
Wireless NO
Colour White
Certificate EN54-5 || EN54-7

Documentation

Language Name Type Action
EN
Certificate
EN
Self-generated File
Image

Comments

There are no comments for the product MORLEY-149.

Estimated Delivery: 1 To 5 Business Days (Depending On The Country)
Repair Services And Technical Support
No Worries: 15 Days Right Of Withdrawal
Secure Transaction
Request technical assistance

Your account does not have your company’s customer code (CLXXXXXX) assigned, therefore this option is not available.

Request the assignment now and, once it is activated, you will be able to access the fastest and most efficient way to obtain technical support.

Thank you! Your request has been submitted.
xs
sm
md
lg
xl