notifier
NOTIFIER-278 | FAAST-LT suction system P / analog loop 1 channel / 2 detectors
NOTIFIER-278FL2012EI-HSFAAST-LT suction system P / analog loop 1 channel / 2 detectors

FAAST-LT suction system P / analog loop 1 channel / 2 detectors

NOTIFIER-278

FL2012EI-HS

Main features

  • FAAST-LT suction system P / analog loop 1 channel / 2 detectors
  • Compatible with central AM-8200

Specifications

 

FAAST-LT system for fume analysis by aspiration of a channel / IP65, with direct connection to the AM-8200 loop model FL2012EI-HS with built-in isolator and local supervised siren output per channel, which includes an addressable control module (01- 159) on the door to monitor power and / or flow failure and two VIEW point sensors with 9 alarm levels and sensitivity prealarms that can be parameterized from the analog detection center.

  • System information by means of a pendulum-shaped graphic bar with 9 air flow levels to verify that the air flows according to the requirements of EN54-20.
  • Internal point detectors that incorporate manual and automatic test functions and decadic addressing (01-159) easily replaceable.
  • Internal record of 2,244 events.
  • Principle of dust discrimination by AWACS ™ algorithms.
  • Includes easy access internal filter (FL-IF) and ultrasonic flow sensor.
  • Configuration via standard USB cable and PipeIQ LT software (included).
  • Compatible with OPAL 159 + 159 protocol (shows speed / flow values ​​per channel).
  • It has 2 sample pipe entries per channel Max. 50 meters each, in a single line of 100 meters and 160 meters in T with up to 18 holes per channel in class C, 6 in class B and 3 in class A.
  • Requires 24 Vdc power supply according to EN54-4.
  • Maximum current consumption: 360mA at 24 Vdc (without sirens and supplied with software justifying design and configuration PipeIQ LT.
REFERENCE / MODEL NOTIFIER-278 / FL2012EI-HS
Loops 1
Number of pipes 1
Display SI

Documentation

Language Name Type Action
EN
Manufacturer's Data Sheet
EN
Self-generated File
Image

Comments

There are no comments for the product NOTIFIER-278.

Repair Services And Technical Support
No Worries: 15 Days Right Of Withdrawal
Secure Transaction
Request technical assistance

Your account does not have your company’s customer code (CLXXXXXX) assigned, therefore this option is not available.

Request the assignment now and, once it is activated, you will be able to access the fastest and most efficient way to obtain technical support.

Thank you! Your request has been submitted.