Features - Power supply oriented as an auxiliary component for powering elements and devices that are part of fire detection and alarm systems - It has monitoring relay and status indicators (network, batteries, outputs and charger) - Input voltage range: 195V ~ 255V AC, 50 / 60Hz - 2 power outputs with a voltage range of 20V ~ 28V DC - Maximum output current of 2A (between both outputs) with battery charge disabled and 1.2A charging batteries - Operating from batteries, the power supply is capable of supplying 2.5A - Space for 2 batteries of 12V DC / 20Ah (380 x 175 x 90 mm) - Charging current of 0.8A batteries - 24 mA control circuit consumption - Maximum resistance of the batteries of 1.5 Ohms - Fault relay: C, NC, NA; maximum 30V DC / 1A - 4A mains fuse - 4A Battery Fuse - Degree of protection IP30 - Dimensions: 400 x 350 x 100 mm - Certified by laboratory according to EN54-4
REFERENCE / MODEL
FOC-611 / FOC-611
Voltage
24V
Amperage
2 A
Documentation
Language
Name
Type
Action
EN
EN_FOC-611_data_sheet
Self-generated File
EN
FOC-611_data_sheet_en.pdf
Manufacturer's Data Sheet
FOC-611
Image
Self-generated File
Manufacturer's Data Sheet
Image
Comments
There are no comments for the product FOC-611.