honeywell
MORLEY-136N | Optical-thermal detector with isolator
MORLEY-136NMI-PTSE-S2I-IVOptical-thermal detector with isolator

Optical-thermal detector with isolator

MORLEY-136N

MI-PTSE-S2I-IV

Main features

  • Morley-IAS photo-thermal multisensor with isolator
  • Honeywell Morley-IAS HMI series
  • Combines two independent sensing elements
  • Includes isolation against short circuits
  • Advanced protocol and software filters against false alarms
  • Integrated dual LEDs for 360° visibility
  • Easy maintenance (washable filter)
  • Ivory color
  • Conforms to EN54-7/5 standards.

Specifications

  • Morley-IAS Optical-Thermal Detector with Isolator
  • Multi-criteria detector uses thermal assistance to the main photoelectric smoke detector to provide greater immunity to false alarms and faster response to a wide range of incipient fires
  • Combines two independent detection elements that are managed by embedded software to act as a single unit
  • Fixed 58°C fixed temperature and temperature rise thermal detection
  • Includes short-circuit isolation
  • Isolator enables faster and more accurate fault location
  • Quick installation with rotary address selectors (01-159)
  • Compatible with Advanced protocol of MORLEY-129 (LT-32), MORLEY-130 (LT-159) and MORLEY-131 (PL-1000) analog control panels
  • Software filters to avoid false alarms
  • Addressable analog communication
  • Integrated dual LEDs for 360° visibility, with three colors for easy status identification: green, yellow and red
  • Max. terminal size: 2.5 mm2
  • Operating voltage: 15V ~ 32V DC
  • Maximum standby current: 200 μA at 24V DC (no communications), 300 μA at 24V DC (LED flashing activated)
  • Isolation current: 15 mA at 24V DC
  • Remote output voltage: 22.5V DC @24V DC
  • Remote output current: 10.8 mA @ 24V DC
  • Maximum continuous current: 1A (switch closed)
  • Operating temperature -30°C ~ +70°C (-30°C ~ +70°C)
  • Operating relative humidity 10% ~ 93% (non-condensing)
  • Mounting base not included: NOTIFIER-77 (B501AP)
  • Made of polycarbonate and ivory-colored ABS plastic
  • Dimensions (mounted on base not included): Ø102 x 61 (H) mm
  • Weight (counting base not included): 99 g
  • Conforms to EN54-7 and EN54-5
  • LPCB approved
  • Environmentally friendly
  • Complies with RoHS legislative requirements
REFERENCE / MODEL MORLEY-136N / MI-PTSE-S2I-IV
Special Protection No
Protocol Advanced
Detector Technology Óptico-Térmico
Base/Cover included NO
Wireless NO
Colour Ivory
Certificate EN54-5 || EN54-7

Documentation

Language Name Type Action
EN
Self-generated File