honeywell-cctv
HWFIRE-3 | CMSI Type B addressable H4YB
HWFIRE-3H4YBCMSI Type B addressable H4YB

CMSI Type B addressable H4YB

HWFIRE-3

H4YB

Main features

  • CMSI Type B addressable Honeywell H4YB
  • Supports 99 pushbuttons, expandable to 198
  • Integrated short-circuit isolator
  • Three configurable safety functions
  • UGA2 function for evacuation
  • Configuration via touch screen
  • Color coding for events
  • Two internal power supplies
  • High energy independence
  • 1 UGA function
  • 3 safety functions
  • Box with integrated UGA and CMSI function
  • Supplied with batteries.

Specifications

  • The CMSI H4YB is a category B addressable device from the Honeywell Fire range, designed for locations such as shopping malls, retail stores, showrooms and sports halls.
  • It has a bus that allows up to 99 manual push buttons or input/output (I/O) devices to be connected.
  • It is expandable to 198 activation points by adding a second bus.
  • Each hand pushbutton or I/O device integrates a short-circuit isolator and handwheels for easy maintenance or component replacement.
  • It offers three fully configurable fail-safe functions, as well as a UGA2 function for evacuation of persons.
  • Easy to install and operate, the CMSI H4YB can be configured from its front touch screen or via the L-HBT software with a KP-H cable.
  • The color touch screen facilitates the identification of events with a color code: red for fire, yellow for faults and blue for technical alarms.
  • It has two internal power supplies: a 24 Vdc 400 mA EAES to power up to 3 H4Y-TRE repeaters, and a 2 A AES that distributes 500 mA to each of the 4 security command lines.
  • This system provides high power independence, often avoiding the need for additional external power supplies.
  • If the evacuation lines are heavily loaded, it is necessary to add an 80545F power module, after having calculated the power balance with dedicated software.
  • Power supply: 230 V~ (AC) +10% / -15%, 50/60 Hz, 130 W
  • Mains fuse: F 4A L 250V
  • Ripple rate: <1 % Vss on load
  • Maximum output current: 0.9 A
  • Minimum output current: 0.1 A
  • Output voltage (range): 20 to 29 V DC
  • Maximum current of 24V auxiliary outputs: 400 mA (electronics)
  • Bus voltage (range): 28 V DC
  • Supplied with batteries
  • Battery fuse: F 2A L 250V
  • Operating temperature: -5°C to +40°C (recommended: +5°C to 35°C)
  • Operating humidity: 5 % to 95 % R.H.
  • Enclosure with integrated UGA and CMSI function
  • Enclosure and door: ABS V0
  • Chassis: Galvanized and painted steel
  • Degree of protection: IP30 (EN 60529)
  • Dimensions: 350 (height) x 380 (width) x 125 (depth) mm
  • Approximate weight: 4 kg (without batteries)
  • UNE-EN 54-2: Fire alarm and fire detection systems - Control and indication equipment
  • UNE-EN 54-4/A2:2006: Fire alarm and fire detection systems - Power supply equipment

The CMSI H4YB is a category B addressable device from the Honeywell Fire range, designed for locations such as shopping malls, stores, showrooms and sports halls.It has a bus that allows up to 99 manual push buttons or input/output (I/O) devices to be connected.It is expandable to 198 activation points by adding a second bus.Each manual push button or I/O device integrates a short-circuit isolator and manual addressing wheels, which facilitates maintenance or component replacement.It offers three fully configurable fail-safe functions, as well as a UGA2 function for evacuation of persons.Easy to install and operate, the CMSI H4YB can be configured from its front touch screen or via the L-HBT software with a KP-H cable.The color touch screen facilitates the identification of events with a color code: red for fires, yellow for faults and blue for technical alarms.It has two internal power supplies: a 24 Vdc and 400 mA EAES to power up to 3 H4Y-TRE repeaters, and a 2 A AES that distributes 500 mA on each of the 4 security command lines.This system provides high energy independence, often avoiding the need for additional external power supplies.If the evacuation lines are heavily loaded, it is necessary to add an 80545F power module, after having calculated the power balance with dedicated software.
Power supply: 230 V~ (AC) +10% / -15%, 50/60 Hz, 130 WMainsupply fuse: F 4A L 250VRipple rate: <1 % Vss on loadMaximum output current: 0.9 ACMinimum output current: 0.1 AT Output voltage (range): 20 to 29 V DCMaximum current of auxiliary outputs 24V: 400 mA (electronic)Bus voltage (range): 28 V DCDelivered with batteriesBattery fuse: F 2A L 250VOperating temperature: -5°C to +40°C (recommended: +5°C to 35°C)Operating humidity: 5 % to 95 % H.R.
Enclosure with integrated UGA and CMSI functionEnclosure and door: ABS V0Chassis: Galvanized and painted steelDegree of protection: IP30 (EN 60529)Dimensions: 350 (H) x 380 (W) x 125 (D) mmApproximate weight: 4 kg (without batteries)
UNE-EN 54-2: Fire alarm and detection systems - Control and indicating equipmentUNE-EN 54-4/A2:2006: Fire alarm and detection systems - Power supply equipment

REFERENCE / MODEL HWFIRE-3 / H4YB
Loops 1
Colour Black
Certificate EN54-2 || EN54-4
Installation environment Indoor

Documentation

Language Name Type Action
EN
Self-generated File
Image

Comments

There are no comments for the product HWFIRE-3.

RELATED PRODUCTS

Repair Services And Technical Support
No Worries: 15 Days Right Of Withdrawal
Secure Transaction
xs
sm
md
lg
xl