FAAST-LT suction system P / analog loop 1 channel / 2 detectors

NOTIFIER-278

FL2012EI-HS


  • FAAST-LT suction system P / analog loop 1 channel / 2 detectors
  • Compatible with central AM-8200

FAAST-LT system for fume analysis by aspiration of a channel / IP65, with direct connection to the AM-8200 loop model FL2012EI-HS with built-in isolator and local supervised siren output per channel, which includes an addressable control module (01- 159) on the door to monitor power and / or flow failure and two VIEW point sensors with 9 alarm levels and sensitivity prealarms that can be parameterized from the analog detection center.

  • System information by means of a pendulum-shaped graphic bar with 9 air flow levels to verify that the air flows according to the requirements of EN54-20.
  • Internal point detectors that incorporate manual and automatic test functions and decadic addressing (01-159) easily replaceable.
  • Internal record of 2,244 events.
  • Principle of dust discrimination by AWACS ™ algorithms.
  • Includes easy access internal filter (FL-IF) and ultrasonic flow sensor.
  • Configuration via standard USB cable and PipeIQ LT software (included).
  • Compatible with OPAL 159 + 159 protocol (shows speed / flow values ​​per channel).
  • It has 2 sample pipe entries per channel Max. 50 meters each, in a single line of 100 meters and 160 meters in T with up to 18 holes per channel in class C, 6 in class B and 3 in class A.
  • Requires 24 Vdc power supply according to EN54-4.
  • Maximum current consumption: 360mA at 24 Vdc (without sirens and supplied with software justifying design and configuration PipeIQ LT.
REFERENCE / MODEL NOTIFIER-278 / FL2012EI-HS
Loops 1
Number of pipes 1
Display SI

There are no comments for the product NOTIFIER-278.