XTRALIS-6VEP-A00-1P
XTRALIS-6
.jpg)
XTRALIS-6
VEP-A00-1P
Main features
Specifications
Features
Aspiration Smoke Detector with Flair analysis chamber, consisting of double laser beam and microscopic vision for Artificial Intelligence analysis of particles.
- Status indicator panel with 7 LED lights and multifunction button.
- Housing in high strength plastic material.
- 7 programmable relays.
- Inlet for 1 pipe, a detection zone.
- Air flow monitoring of the sampling pipe.
- Air filter with control chip.
- Sensitivity range from 0.005 to 20% dimming per meter.
- 4 alarm levels (Alert, Action, 1st level of fire and 2nd level of fire), with sensitivity adjustment in each one.
- Maximum coverage area: 2,000 m2.
- Maximum pipe length of up to 130 m. (not included).
- Advanced data connection: VesdaNet, Ethernet and WiFi.
- E-mail engine and services for connection with Smartphone.
- Event log for more than one year of operation history.
- AutoLearn: Examines the environment, selects the most appropriate alarm levels and adjusts the air flow sensors automatically.
- Requires external 24 Vdc power.
EN-54/20 Certificate - CPR and CE Marking. Class A: 30 sampling shots - Fire Threshold at 0.015% obs / m. Class B: 40 sampling points - Fire Threshold at 0.026% obs / m. Class C: 45 sampling points - Fire Threshold at 0.062% obs / m.
REFERENCE / MODEL | XTRALIS-6 / VEP-A00-1P |
---|---|
Loops | 1 |
Number of pipes | 1 |
Display | SI |