esser
ESSER-33 | Gateway IQ8Control C
ESSER-33808003Gateway IQ8Control C

Gateway IQ8Control C

ESSER-33

808003

Main features

  • Gateway algorithmic fire detection
  • Software addressable
  • Expandable from 1 to 2 loops of 127 elements each
  • IQ8Control systems can manage Esser's high performance analog equipment
  • Approved by VdS and manufactured according to EN54 parts 2, 4 and 13
  • Composed of basic equipment (CPU, power supply and box)
  • Incorporates a slot for micro-modules on motherboard
  • Expandable to 2 slots with expansion board 772477.

Specifications

Specifications

  • Gateway algorithmic fire detection
  • Requires ESSER-42 front display (786006)
  • Up to 2 micro module slots
  • Up to 2 analog loops (254 devices) as isolated Gateway or 1 loop (127 devices) as Gateway essernet network
  • Up to 1000 zones and 1000 outputs
  • Analog loop protected against short-circuit or open circuit
  • Loop wiring 2-wire x 0.8 mm2 to 2.5 mm2 shielded braided hose, up to 3.5 km depending on the load
  • Up to 127 devices per analog loop configurable in up to 127 zones per loop
  • Up to 32 transponders per analog loop
  • Maximum load factor per loop, 96 (esserbusPLus): Up to 48 IQ8Quad detectors with siren or flash (Load factor 2); up to 32 sirens/detectors with voice/siren and flash (Load factor 3)
  • Maximum load factor per Gateway, 384: Up to 96 IQ8Quad detectors with siren or flash (Load factor 2); up to 64 sirens/detectors with voice/siren and flash (Load factor 3)
  • Up to 3 freely programmable relays as supervised, voltage output 12V or dry contact up to 24V/1A (with expander 772477)
  • TTY or RS485 protocol output
  • Optional micro-module/converter for matrix printer connection or basic RS-232 protocol output
  • Connection of up to 31 LCD repeater panels with RS485 displays
  • 62.5 kBd or 500 KBd essernet network for up to 31 devices (control panels, network repeaters with keypad or SEI-KIT communications interface)
  • 10,000 event history
  • Supervision and charging circuit for 2 emergency batteries
  • Connection to TG-ESSER management software via SEI-KIT network interface (requires essernet network connection) with complete protocol
  • Power supply: 230V AC, 50/60Hz
  • Power supply output voltage: 12V DC
  • Current consumption: 300 mA without front-end, 340 mA with front-end
  • Nominal consumption: 0.7A
  • Maximum external current: 2A
  • Operating temperature: -5°C ~ +45°C
  • Dimensions: 450 (W) x 320 (H) x 185 mm
  • Weight: 6.5 kg
REFERENCE / MODEL ESSER-33 / 808003
Loops 2
Connectivity RS232 || RS-485

Documentation

Language Name Type Action
DE
Self-generated File
Image

Comments

There are no comments for the product ESSER-33.

RELATED PRODUCTS

Estimated Delivery: 1 To 5 Business Days (Depending On The Country)
Repair Services And Technical Support
No Worries: 15 Days Right Of Withdrawal
Secure Transaction
xs
sm
md
lg
xl