- Gateway algorithmic fire detection
- Software addressable
- Expandable from 1 to 2 loops of 127 elements each
- IQ8Control systems can manage Esser's high performance analog equipment
- Approved by VdS and manufactured according to EN54 parts 2, 4 and 13
- Composed of basic equipment (CPU, power supply and box)
- Incorporates a slot for micro-modules on motherboard
- Expandable to 2 slots with expansion board 772477.
- CCTV
- Intercom
- Toegangscontrole
- Alarmsystemen
- Brand
- Networking
- IOT SmartHome
- SIM-kaarten
- Cyberbeveiliging
ALARM.COM Systemen
Alarm VESTA
Medisch Alarm VESTA
U-PROX Systemen
PYRONIX/HIKVISION SYSTEMEN
HONEYWELL® systemen
PARADOX® systemen
VISONIC Systemen
DSC® Systemen
Doe het zelf Klasse 1 Alarmsystemen
Alarm overdragers en ontvangers
Bewegingsmelders
Schok en tril detectoren
Magneetcontacten
Speciale detectoren
Perimeter detectie
Sirenes
Mistgeneratoren
Proactieve Rook generator
Kabels
Accessoires

ESSER-33808003Gateway IQ8Control C
ESSER-33

Gateway IQ8Control C
ESSER-33
808003
This product is discontinued
Hoofd functies
Specificaties
Specifications
- Gateway algorithmic fire detection
- Requires ESSER-42 front display (786006)
- Up to 2 micro module slots
- Up to 2 analog loops (254 devices) as isolated Gateway or 1 loop (127 devices) as Gateway essernet network
- Up to 1000 zones and 1000 outputs
- Analog loop protected against short-circuit or open circuit
- Loop wiring 2-wire x 0.8 mm2 to 2.5 mm2 shielded braided hose, up to 3.5 km depending on the load
- Up to 127 devices per analog loop configurable in up to 127 zones per loop
- Up to 32 transponders per analog loop
- Maximum load factor per loop, 96 (esserbusPLus): Up to 48 IQ8Quad detectors with siren or flash (Load factor 2); up to 32 sirens/detectors with voice/siren and flash (Load factor 3)
- Maximum load factor per Gateway, 384: Up to 96 IQ8Quad detectors with siren or flash (Load factor 2); up to 64 sirens/detectors with voice/siren and flash (Load factor 3)
- Up to 3 freely programmable relays as supervised, voltage output 12V or dry contact up to 24V/1A (with expander 772477)
- TTY or RS485 protocol output
- Optional micro-module/converter for matrix printer connection or basic RS-232 protocol output
- Connection of up to 31 LCD repeater panels with RS485 displays
- 62.5 kBd or 500 KBd essernet network for up to 31 devices (control panels, network repeaters with keypad or SEI-KIT communications interface)
- 10,000 event history
- Supervision and charging circuit for 2 emergency batteries
- Connection to TG-ESSER management software via SEI-KIT network interface (requires essernet network connection) with complete protocol
- Power supply: 230V AC, 50/60Hz
- Power supply output voltage: 12V DC
- Current consumption: 300 mA without front-end, 340 mA with front-end
- Nominal consumption: 0.7A
- Maximum external current: 2A
- Operating temperature: -5°C ~ +45°C
- Dimensions: 450 (W) x 320 (H) x 185 mm
- Weight: 6.5 kg